lymereJ
left a comment
There was a problem hiding this comment.
Code walk-through:
| NotModulated, | ||
| LeavingSetpointModulated, | ||
| VariableSpeedPump, | ||
| Variable, |
There was a problem hiding this comment.
Similar to what's already there but I feel like Variable fits better here since this equipment is on the demand side, VariableSpeedPump felt more like a supply side term. Also VariableFlow better aligns with ConstantFlow that already exists.
| SetupOutputVariable(state, | ||
| "Coil Cooling ITE Cold Plate Effective Thermal Resistance", | ||
| Constant::Units::K_W, | ||
| this->effectiveThermalResistance, | ||
| OutputProcessor::TimeStepType::System, | ||
| OutputProcessor::StoreType::Average, | ||
| this->name); |
There was a problem hiding this comment.
This variable was not included in the NFP at the time it was presented to the team. The output is predictable and can be obtained by multiplying the nominal thermal resistance by the curve output but I felt like this might be more convenient and contribute to better transparency of the model to the users.
| A10, \field IT Equipment Load Schedule Name | ||
| \note Optional schedule specifying an IT equipment heat load in watts added to any load set by | ||
| \note a paired ElectricEquipment:ITE:LiquidCooled object. When both are present their | ||
| \note contributions are summed. When no paired object exists this schedule is the sole load source. | ||
| \type object-list | ||
| \object-list ScheduleNames |
There was a problem hiding this comment.
This proposed input was not included in this document at the time this NFP was presented. I'm proposing to add it for two reasons: 1) I think this gives users the flexibility to add simple schedule driven loads, 2) It allows this feature to be tested independently of the concurrent ElectricEquipment:ITE:LiquidCooled. Since this adding this input was not discussed, I'd be happy to remove it if the team does not want it.
| N7; \field Sizing Factor | ||
| \note Multiplies the design load used to autosize the nominal liquid flow rate. Use a value less than 1.0 | ||
| \note when several cold plates share the cooling load, for example 1/X for X identical cold plates. | ||
| \note Applies to autosizing only. | ||
| \type real | ||
| \minimum> 0.0 | ||
| \default 1.0 |
There was a problem hiding this comment.
Same, this was not in this document at the time this NFP was presented.
| // When there is a load but no active cooling, report the maximum case temperature (same as the zero-flow guard below). | ||
| // This is a reporting convention, not a prediction: without cooling a real chip would exceed this limit, and there is no | ||
| // transient chip model (Tc = f(t, load)) to represent the thermal mass or the time taken to heat up. | ||
| this->caseTemperature = (load > 0.0) ? this->maximumCaseTemperature : 0.0; |
There was a problem hiding this comment.
See the convention mentioned in the comment. I welcome opinion/advice on this. Would the last know temperature be better?
There was a problem hiding this comment.
I think so. Given there is a maximum and target case temperature I think I would leave it at whatever it was when the load transitioned to 0. I think that would be better than seeing 0's when there was no load. Also, the case temperature figure shows both target and max case temps when there is a load so maybe not even set the caseTemperature right here and leave it at whatever is was when there was a load.
this->caseTemperature = (load > 0.0) ? this->maximumCaseTemperature : this->inletTemperature;
There was a problem hiding this comment.
Sounds good, I've made the change.
| ! This file is not intended to represent an actual data center. The building, loads, schedules, | ||
| ! temperatures and equipment are simplified, and are only meant to exercise the cold plate object. |
There was a problem hiding this comment.
Important note about this example file. It could perhaps be removed when ElectricEquipment:ITE:LiquidCooled is available and we develop a proper datacenter example file.
| ! The thermal resistance modifier curve (Curve:Exponent) was obtained by fitting an exponent curve | ||
| ! through data published in peer-reviewed sources. It is intended to represent a typical modification | ||
| ! of the thermal resistance with the flow rate for the "Standard" thermal resistance approach. |
There was a problem hiding this comment.
I could share a plot with the data in the engineering manual if need be.
| this->name, | ||
| this->loadFromITEquipment)); | ||
| } | ||
| Real64 const load = this->loadFromITEquipment + loadFromSchedule; |
There was a problem hiding this comment.
We could also add a one time warning if both an IT equipment AND schedule load exist, but maybe it's fine as it is.
| A11, \field Nominal Flow Rate Sizing Basis | ||
| \note Basis of the design load used to autosize the nominal liquid flow rate. The autosized maximum | ||
| \note liquid flow rate, which equals the nominal flow rate, and the flow rate registered with the plant | ||
| \note loop follow the same design load. | ||
| \note ColdPlateCapacity: the heat the cold plate transfers at the Target Case Operating Temperature, the | ||
| \note Sizing:Plant design loop exit temperature and the nominal thermal resistance. | ||
| \note MaximumITELoad: the maximum value of the IT Equipment Load Schedule Name, limited to the heat the | ||
| \note cold plate transfers at the Maximum Case Temperature. Requires the IT Equipment Load Schedule Name. | ||
| \note Placeholder: until the ElectricEquipment:ITE:LiquidCooled object is available, the design load is taken from | ||
| \note the IT Equipment Load Schedule Name only. When it is available, the design load of the paired object will also | ||
| \note be used, and the schedule will no longer be required for a cold plate that has a paired object. | ||
| \type choice | ||
| \key ColdPlateCapacity | ||
| \key MaximumITELoad | ||
| \default ColdPlateCapacity |
There was a problem hiding this comment.
This was also not in this document at the time this NFP was presented. This new input gives more flexibility in terms of sizing the cold plate: plant loop sizing data or design load.
| A12; \field Follow IT Equipment Multipliers | ||
| \note A cold plate object stands for N identical cold plates. The flow rates, the auxiliary electric power and | ||
| \note the thermal resistance of this object are for one cold plate. The heat transfer, mass flow rate and | ||
| \note auxiliary electric outputs are totals for N cold plates. | ||
| \note ITEMultiplierAndZoneMultiplier: N is the product of the Multiplier of the ElectricEquipment:ITE:LiquidCooled | ||
| \note object that refers to this cold plate and the zone multipliers (zone multiplier times zone list multiplier) | ||
| \note of the zone of that object. | ||
| \note None: N is 1. The object is an aggregate of all the racks and of all the copies of the zone. | ||
| \note It is incorrect to use None in a zone with a zone multiplier greater than 1. | ||
| \note Placeholder: the ElectricEquipment:ITE:LiquidCooled object is not available yet. Until it is, the multiplier of | ||
| \note that object and the multipliers of its zone are taken as 1, and ITEMultiplierAndZoneMultiplier follows the | ||
| \note zone multipliers of the zone of this cold plate. This note will be updated when the object is available. | ||
| \type choice | ||
| \key ITEMultiplierAndZoneMultiplier | ||
| \key None | ||
| \default ITEMultiplierAndZoneMultiplier |
There was a problem hiding this comment.
This was also not in this document at the time this NFP was presented. This lets the user specify how to track the various multipliers that come into play.
| Real64 loadLimit = 0.0; // heat the cold plate transfers at the maximum case temperature [W] | ||
| bool loadWasLimited = false; // true if the design load was limited to loadLimit | ||
| if (loadBased) { | ||
| scheduleMaxLoad = this->itLoadSchedule->getMaxVal(state); |
There was a problem hiding this comment.
Get the schedule "load-based" design load by taking the maximum value out of the user specified load scheduled. Note that this value will be added to the value returned byGetITEColdPlateDesignLoadPerPlate once #11667 is merged. Both values are per cold plate.
There was a problem hiding this comment.
Confirmed here. per-plate on both sides, not rack-Multiplier-scaled
| // The object stands for every copy of its zone: the heat removed by the coolant is the heat of all copies, and the zone heat | ||
| // gain is per copy | ||
| stored.plateZoneMultiplier = state.dataHeatBal->Zone(zoneIndex).Multiplier * state.dataHeatBal->Zone(zoneIndex).ListMultiplier; | ||
|
|
||
| // Number of plates the object represents. | ||
| // This block is the rule for a cold plate without a paired IT equipment object: nIte = 1 and nZone follows the zone of this | ||
| // object, and None is an error in a multiplied zone. It stays when the ElectricEquipment:ITE:LiquidCooled object is available. | ||
| // Until then no cold plate has a paired object. For a paired cold plate, the link made when this object is created overrides | ||
| // these values with nIte = Multiplier of the paired object and nZone = multipliers of the zone of the paired object, and applies | ||
| // the None check to that zone. | ||
| stored.nIte = 1.0; | ||
| if (stored.followMultipliers == FollowMultipliers::ITEMultiplierAndZoneMultiplier) { | ||
| stored.nZone = stored.plateZoneMultiplier; | ||
| } else { | ||
| // The object stands for one copy of the zone only, so the heat of the other copies of a multiplied zone would be lost | ||
| stored.nZone = 1.0; | ||
| if (stored.plateZoneMultiplier > 1.0) { | ||
| ShowSevereError( | ||
| state, | ||
| std::format("{}: Follow IT Equipment Multipliers = None is not allowed for object \"{}\" because zone \"{}\" has a " | ||
| "zone multiplier of {:.0f}.", | ||
| cCurrentModuleObject, | ||
| stored.name, | ||
| zoneName, | ||
| stored.plateZoneMultiplier)); | ||
| ShowContinueError(state, "Use ITEMultiplierAndZoneMultiplier, or a zone without a zone multiplier."); | ||
| errorsFound = true; | ||
| } | ||
| } |
There was a problem hiding this comment.
Handling zone and IT equipment multipliers at input processing.
| Zone One, !- Zone Name | ||
| VariableFlow, !- Flow Mode | ||
| ColdPlateAuxiliary, !- End-Use Subcategory | ||
| ITELoad; !- IT Equipment Load Schedule Name |
There was a problem hiding this comment.
It's never a good idea to have a single instance of a component in a new model. Either add another to the same zone or add another zone with another ITE coil. Might even be a good idea to do both of these.
There was a problem hiding this comment.
Thanks, I've added a second cold plate to this model. We'll also have an example file more representative of a datacenter once all related PR are merged. I'll update the plots above shortly.
| \ip-units W | ||
| \minimum 0.0 | ||
| \default 0.0 | ||
| A7 , \field Zone Name |
There was a problem hiding this comment.
@lymereJ @yujiex Is there ever a situation where you expect the cold plate to not be in the same room as the rack in which it sits? You are specifying the zone/space over on the parent object, too. I guess I don't see why we would want to specify it in both locations?
There was a problem hiding this comment.
I don't have a good example, but I like that this gives users the flexibility to do so. Also, if a user uses the schedule-based load approach without a parent IT equipment object, that field becomes relevant. What if we default the field to the parent object's value when the user hasn't specified it and a parent object exists?
There was a problem hiding this comment.
You think we should allow using this alone without the parent object?
There was a problem hiding this comment.
The example file in this PR doesn't use a parent object. Instead, the cold plate load comes from a schedule. A user taking the same approach would need to use that field. I'm not necessarily recommending this approach, but it could be a valid option for someone who wants a simpler model.
There was a problem hiding this comment.
How is the liquid-air spilt applied?
There was a problem hiding this comment.
The cold plate captures what it can, the rest is added as convective heat gains to the zone.
There was a problem hiding this comment.
There was a problem hiding this comment.
Not if a parent object is used.
There was a problem hiding this comment.
Sorry, but I'm going need a better explanation. You can determine the liquid-air split from cold plate model's inherent methods, but now when a parent object is present you fallback to the prescribed value?
There was a problem hiding this comment.
It's not a fallback to a prescribed value. There are two different splits, applied in series:
- Which heat is routed to the cold plate at all (parent only). ElectricEquipment:ITE:LiquidCooled applies Liquid Heat Capture Fraction to say how much of the rack's heat is on the liquid path by design. The rest was never meant to go to the coolant, and it goes to the parent's Zone.
- How much of the routed heat the plate can remove (cold plate, always). The cold plate computes its capacity from thermal resistance, flow, coolant inlet temperature and maximum case temperature. It removes min(routed load, capacity), and the shortfall goes to the Zone Name on the coil.
With no parent, step 1 doesn't exist. The IT Equipment Load Schedule is the heat on the plate (an implicit capture fraction of 1), and only step 2 applies. The example file does this.
So the two zone fields aren't duplicates when a parent is present: the parent's zone receives the by-design air fraction, and the coil's zone receives the capacity shortfall. The coil's field is required because it is the only place the shortfall can go in the standalone case.







Pull request overview
This PR introduces a new plant object for modeling direct-to-chip cooling for
ElectricEquipment:ITE:LiquidCooledobjects, which are being developed concurrently (see NFP in #11667).Pull Request Author
Reviewer