The flow battery allows for limiting cells based on power, current, or both.
For this case, limiting power results in 6,000,015 cells:
Limiting current results in 4,285,715
Limiting both should result in the larger number, but results in the current limited number due to internal logic:
This means that the maximum output of the battery is 50.96 MW, when 60 MW was specified.
This will be updated as a part of the transition to SSC equations for battery sizing.